2-Loop Addressable Intelligent Fire Alarm Control Panel
The GST 200-2 single loop and two loop addressable fire detection control panel is packed with features that are not usually associated with smaller and medium systems. The GST 200-2 provides a high quality solution at exceptional value.
Product Details
| FEATURES |
|---|
| Loop capacity 477 intelligent devices |
| 30 logical configurable zones |
| PAS and Acknowledge Function |
| Duplicate address report |
| Mismatch device type report |
| Dirty Detector Reporting |
| One Man Test Function |
| Graphical LCD Display |
| Zone indication and manual intervention panel |
| Net-workable with all GST intelligent fire panels |
| Programmable from PC |
| Built-in RS485 repeater output (Maximum 10 repeaters) |
| Optional GMC graphic station |
| Optional Panel Printer |
| Advanced user friendly programming software including ‘Fuzzy Logic’ |
| Optional protection of re-programming |
| LPCB approved |
| NAME | DETAILS |
|---|---|
| Standard | EN54 Part 2/4 |
| Approvals | LPCB, CE |
| Main Input Voltage | 220/230 VAC (+10/-15%) 50/60 Hz |
| Input Current Rating | 0.5A |
| System Operating Voltage | 24 VDC Nominal |
| Loop Capacity | Loop 1: 235; Loop 2: 242 |
| Outputs (3) | Fire Alarm Output: 500mA /24Vdc/NO-NC F.P.E. Output: 500mA /24Vdc/NO-NC |
| Sounder Circuit Output | 500mA /24Vdc/NO-NC |
| Dimension | (HWD) 580 x 420 x 202 mm |