UL Addressable Output Module
I-M9301 Addressable Output Module works in two-wire mode. On receiving start command from the fire alarm control panel (FACP), it will close the output relay to output normally-open normally closed contact signal and illuminate the Active indicator.
Product Details
FEATURES |
---|
Single output module |
Loop powered for dry contact relay output. Additional 24VDC is required for power output |
Connection mode can be set by handhold programmer (P-9910B) |
Power output line is monitored for cable fault |
Electronically addressed |
Two part plug-in construction with base mounted termination allows easy installation and connection |
Intelligent interface can be addressed and plugged in to base at time of commissioning |
NAME | DETAILS |
---|---|
Operating Voltage | 24VDC |
Operating Current | Loop Standby Current 2mA Action Current 3mA Power Standby Current <5mA Action Current <20mA |
Output Capacity | Dry contact relay: 2A/24VDC Power output: 1A/24VDC |
Operating Environment | Temperature: 0℃ ~+49℃ Relative Humidity: 93% |
Dimension | 120mm x 80mm x 43mm |