UL Intelligent Photoelectric Smoke Detector
DI-M9102, the detector can form fire alarm system connecting with a fire alarm control panel (FACP). The detector illuminates indicators to indicate fire condition and transmits alarm signals to the FACP.
Product Details
FEATURES |
---|
Fault self-diagnostic |
A magnet test available |
Providing for connections to remote indicators |
Built-in microprocessor stores 14 history data |
Polling LED can be set to OFF |
Standard: UL268 |
NAME | DETAILS |
---|---|
Operating Voltage | Loop 24VDC (16VDC~28VDC) |
Operating Current | Standby current: 0.8mA Alarm current: ≤1.8mA (w/o remote indicator), ≤ 3.8mA (w/ remote indicator) |
Sensitivity Range | 1.23%~3.20% per ft |
Operating Environment | Temperature: 0℃ ~+37.8℃ Relative Humidity: 95% |
Dimensions | Diameter: 100mm Height: 44.5mm (without base) |